Know what’s in your water before anyone recommends equipment.
South Blount County Utility District (SBCUD) says its water meets all of EPA’s health standards and that it tested for more than 80 contaminants, in its 2026 report covering 2025[1]. In plain English, the report shows soft[2] Tellico Lake water with chlorine at the tap and byproducts under federal limits on the running average. It also marks “Yes” in the violation column for bacteria samples in May 2025 and for 2024 lead sampling, and notes a reporting violation; all are explained below with the follow-up SBCUD reports. EPA’s PFAS testing found none at or above its reporting levels[3].
By sending this form, you agree that we may call or email you about your request. Texts are sent only if you check the box above.
SBCUD’s water is surface water from Tellico Lake[1]. TDEC rates the source “reasonably susceptible” to potential contamination[1]. That rating describes the untreated lake water, based on geology and human activity nearby, which is why the water is treated and tested before it reaches homes. SBCUD’s water board meets the first Tuesday of each month at 320 Partnership Parkway[1].
| What SBCUD measured | Result | What it means at home |
|---|---|---|
| Hardness | Average 49 ppm[1] | Soft on the USGS scale (0–60 mg/L)[2] |
| Alkalinity / pH | Average 51 ppm / 7.79[1] | Part of the water’s mineral balance |
| Iron / manganese | 0.03 ppm / 0.011 ppm[1] | From SBCUD’s additional monitoring |
| Chlorine | Running annual average 1.72 ppm; range 1.27–2.28[1] | Still in the water at your tap, shower and laundry; the limit is 4 ppm |
| Trihalomethanes | Highest locational running average 49 ppb; results 27–58[1] | Chlorination byproducts; federal limit 80 ppb |
| Haloacetic acids | Highest locational running average 47 ppb; results 28–75[1] | Chlorination byproducts; federal limit 60 ppb |
| Lead (2024) | 90th percentile 4.0 ppb; 2 of 30 samples exceeding the 15 ppb action level[1] | The action level is 15 ppb; see the lead section |
| Copper (2024) | 90th percentile 0.185 ppm; 0 of 30 samples exceeding the action level[1] | The action level is 1.3 ppm |
| Fluoride | 0.3143 ppm; range 0.182–0.387[1] | Federal limit 4 ppm |
| Nitrate / sodium | 0.107 ppm / 7.33 ppm[1] | Low |
| Turbidity | Highest 0.04 NTU; 100% of monthly samples below 0.3 NTU[1] | A measure of how well the plant filters |
| PFAS (EPA testing) | None at or above EPA reporting levels in four 2024 samples[3] | See the PFAS section below |
Soft. SBCUD reports an average hardness of 49 ppm[1], and USGS classifies 0 to 60 mg/L as soft[2]. That means a water softener is usually not the first conversation for South Blount homes on utility water. The more common questions are chlorine taste and smell, and what your own plumbing adds. Homes on private wells are not covered by this report, and a free in-home water test shows what’s in yours.
SBCUD’s table marks “Yes” in the violation column for total coliform bacteria and for fecal coliform and E. coli. It lists two positive total coliform samples, on May 14 and May 15, 2025, and one positive fecal coliform and E. coli sample, on May 15, 2025[1]. The report says SBCUD was required to complete a Level 2 assessment because it found E. coli in its water system. A Level 2 assessment is a very detailed study of the water system to identify potential problems and determine, if possible, why an E. coli MCL violation has occurred and/or why total coliform bacteria have been found in the water system on multiple occasions. The report also says SBCUD was required to take 1 corrective action and completed 1 corrective action[1]. Separately, the report lists a content/delivery rule violation on its 2025 report: required health-effects wording for the lead action level exceedances was not included in the data table. SBCUD says it has corrected this by adding the wording as a footnote to the lead results[1]. The table also marks “Yes” for lead; see the lead section below. For questions, SBCUD’s report lists 865-982-3560[1].
SBCUD’s latest lead and copper sampling was in 2024. The 90th percentile for lead was 4.0 ppb, under the 15 ppb action level, and 2 of 30 samples exceeded the action level; results ranged from below 1.0 to 26.6 ppb[1]. The table’s violation column reads “Yes” for lead[1]. Copper’s 90th percentile was 0.185 ppm, and 0 of 30 samples exceeded its action level[1]. SBCUD’s report explains that lead mainly comes from service lines and home plumbing, recommends cold water for drinking, cooking and baby formula, and flushing your pipes for several minutes before using tap water for those[1]. It also says a filter certified to reduce lead is effective[1]. Reverse osmosis at the kitchen tap is one common way to do that. If you want your water tested for lead, the report says to contact SBCUD at 865-982-3560, and its lead service line inventory is on its website[1].
SBCUD’s chlorine averaged 1.72 ppm over the year, under the 4 ppm limit[1]. Byproducts are reported as the highest locational running annual average: 49 ppb for trihalomethanes against an 80 ppb limit, and 47 ppb for haloacetic acids against a 60 ppb limit[1]. Single haloacetic acid results ranged from 28 to 75 ppb. SBCUD’s table lists the highest locational running annual average against the 60 ppb limit and shows “No” in the violation column[1]. If chlorine taste or smell bothers you, carbon filtration reduces it, at one tap or with whole-house water filtration.
SBCUD’s report says no UCMR 5 unregulated contaminants were above the reporting level[1]. EPA’s data agree: four samples in 2024 (February, May, August and November) at the entry point EPA labels “Entry Point A” at the Tellico Lake Plant showed none of the 29 PFAS EPA tested for, including PFOA and PFOS, at or above EPA’s reporting levels; for PFOA and PFOS that level is 4 ppt[3]. EPA’s limit for PFOA and for PFOS is 4 ppt, measured as a running annual average, with compliance due in 2029; a rule EPA proposed in May 2026 would let systems ask for an extension to 2031[4].
If your water comes from another utility or a private well, this report does not apply to your home. See our Maryville and Blount County page and the other guides on our water quality reports page.
SBCUD’s 2026 report says its water meets all of EPA’s health standards. The same report lists positive total coliform and E. coli samples in May 2025, a Level 2 assessment SBCUD was required to complete, 1 corrective action that SBCUD reports it completed, and 2024 lead sampling where 2 of 30 samples exceeded the 15 ppb action level. The full report and SBCUD at 865-982-3560 are the best sources; a free in-home test shows your own tap.
South Blount County Utility District treats surface water from Tellico Lake. TDEC rates the source reasonably susceptible to potential contamination, a rating about the untreated lake water, which is why it is treated and tested before delivery.
Soft. SBCUD reports an average hardness of 49 ppm, and the USGS scale classifies 0 to 60 mg/L as soft. Iron averaged 0.03 ppm and manganese 0.011 ppm in the report’s additional monitoring.
In SBCUD’s 2024 sampling, the 90th percentile for lead was 4.0 ppb, under the 15 ppb action level, and 2 of 30 samples exceeded the action level. Lead mostly comes from service lines and home plumbing; SBCUD recommends cold water for drinking and says a certified filter is effective. To have your water tested for lead, the report says to contact SBCUD at 865-982-3560.
SBCUD reports no UCMR 5 contaminants above the reporting level. EPA’s data show four 2024 samples at the Tellico Lake Plant with none of the 29 PFAS tested at or above EPA’s reporting levels, including PFOA and PFOS, whose reporting level is 4 ppt.
Perfected Water. Purified Air. Peace of Mind. It starts with a free in-home test.
Call (865) 269-9007 for a free water test · Book a free in-home water test
Book a free in-home water test
All sources opened November 2026.




























By sending this form, you agree that we may call or email you about your request. Texts are sent only if you check the box above.